Condensation of Ozone-Safe Refrigerants in Horizontal Tubes: Experimental Test Facility and Preliminary Results
Bonhomme, D.M.
Loading…
Permalink
https://hdl.handle.net/2142/9695
Description
Title
Condensation of Ozone-Safe Refrigerants in Horizontal Tubes: Experimental Test Facility and Preliminary Results
Author(s)
Bonhomme, D.M.
Contributor(s)
Mainland, M.E.
Hinde, D.K.
Chato, J.C.
Issue Date
1991-10
Keyword(s)
evaporation and condensation
Abstract
A single tube condenser test facility capable of measuring heat transfer coefficient of
condensing refrigerants in horizontal tube has been built and implemented at the Air
Conditionning and Refrigeration Center at the University of lllinois. Baseline testing with
CFC-12 and preliminary testing with HFC-134a has been done. For CFC-12 the
experimental data was within ± 20% of the Shah correlation, ±27% of the Traviss
correlation and ±25% of the CavaIlini-Zecchin correlation. Due to its higher liquid thermal
conductivity the heat transfer coefficient for HFC-134a was higher than that of CFC-12 by
as much as 22%.
Publisher
Air Conditioning and Refrigeration Center. College of Engineering. University of Illinois at Urbana-Champaign.
Series/Report Name or Number
Air Conditioning and Refrigeration Center TR-06
Type of Resource
text
Language
en
Permalink
http://hdl.handle.net/2142/9695
Sponsor(s)/Grant Number(s)
Air Conditioning and Refrigeration Center Project 01
Use this login method if you
don't
have an
@illinois.edu
email address.
(Oops, I do have one)
IDEALS migrated to a new platform on June 23, 2022. If you created
your account prior to this date, you will have to reset your password
using the forgot-password link below.