Experimental Investigation of Void Fraction During Horizontal Flow in Larger Diameter Refrigeration Applications
Wilson, M.J.
Loading…
Permalink
https://hdl.handle.net/2142/11849
Description
Title
Experimental Investigation of Void Fraction During Horizontal Flow in Larger Diameter Refrigeration Applications
Author(s)
Wilson, M.J.
Contributor(s)
Newell, T.A.
Chato, J.C.
Issue Date
1998-07
Keyword(s)
void fraction
Abstract
"Void fractions were measured for R134a and R410A for a smooth tube with inside
diameter of 6.12 mm (0.241""), an axially grooved tube of base diameter 8.89 mm
(0.350""), and a 18° helically grooved of base diameter 8.93 mm (0.352""). The experiment
covered mass fluxes from 75 kg/m2s to 700 kg/m2s (55 - 515 klbnJ'ft2-hr) and average test
section qualities from 5% to 99% with an inlet temperature of 5°C (41°F). Several
existing models are examined for accuracy and a simple adjusted model is presented to
accurately predict the data and data presented in a companion study by Yashar[1998].
The experimental apparatus and methodology are also discussed."
Publisher
Air Conditioning and Refrigeration Center. College of Engineering. University of Illinois at Urbana-Champaign.
Series/Report Name or Number
Air Conditioning and Refrigeration Center TR-140
Type of Resource
text
Language
en
Permalink
http://hdl.handle.net/2142/11849
Sponsor(s)/Grant Number(s)
Air Conditioning and Refrigeration Center Project 74