Experimental Investigation of Void Fraction During Horizontal Flow in Larger Diameter Refrigeration Applications
Wilson, M.J.
Content Files
TR140.pdf
Loading…
Download Files
Loading…
Download Counts (All Files)
Loading…
Edit File
Loading…
Permalink
https://hdl.handle.net/2142/11849
Description
Title
Experimental Investigation of Void Fraction During Horizontal Flow in Larger Diameter Refrigeration Applications
Author(s)
Wilson, M.J.
Contributor(s)
Newell, T.A.
Chato, J.C.
Issue Date
1998-07
Keyword(s)
void fraction
Date of Ingest
2009-05-18T18:14:58Z
Abstract
"Void fractions were measured for R134a and R410A for a smooth tube with inside
diameter of 6.12 mm (0.241""), an axially grooved tube of base diameter 8.89 mm
(0.350""), and a 18° helically grooved of base diameter 8.93 mm (0.352""). The experiment
covered mass fluxes from 75 kg/m2s to 700 kg/m2s (55 - 515 klbnJ'ft2-hr) and average test
section qualities from 5% to 99% with an inlet temperature of 5°C (41°F). Several
existing models are examined for accuracy and a simple adjusted model is presented to
accurately predict the data and data presented in a companion study by Yashar[1998].
The experimental apparatus and methodology are also discussed."
Publisher
Air Conditioning and Refrigeration Center. College of Engineering. University of Illinois at Urbana-Champaign.
Series/Report Name or Number
Air Conditioning and Refrigeration Center TR-140
Type of Resource
text
Genre of Resource
Technical Report
Language
en
Permalink
http://hdl.handle.net/2142/11849
Sponsor(s)/Grant Number(s)
Air Conditioning and Refrigeration Center Project 74