Abstract
A mathematical model of adiabatic refrigerant flow through capillary tubes is presented.
When using this model for R22, Chen et al.' s metastable model was improved by a correction
factor related to Reynolds number. The resulting model can predict most of the experimental data
for R22 within ±5%. For R134a, with the original metastable correction, the model predicted most
of the experimental data with ±6% except that having subcooling less than about 5°F.
Publisher
Air Conditioning and Refrigeration Center. College of Engineering. University of Illinois at Urbana-Champaign.
Series/Report Name or Number
Air Conditioning and Refrigeration Center TR-139
Type of Resource
text
Language
en
Permalink
http://hdl.handle.net/2142/11848
Sponsor(s)/Grant Number(s)
Air Conditioning and Refrigeration Center Project 69